GDJB-6000D Smart Substation Relay Protection Test System
GDJB-6000D yakashongedzerwa nepamusoro-inoshanda simba amplifier uye yakavakirwa pane ine simba PowerPC+ X86 chikuva.Iyo inotora modular dhizaini uye ine mabasa ane simba, yakanyanya kurongeka, saizi diki uye huremu huremu maficha.Inogona kuyedza basa nekuita kwekubatanidza chikwata, relay kudzivirira mudziyo, kuyerwa uye kudzora mudziyo, akangwara zviteshi etc. Very akakodzera zvirimwa simba, substations, siyana tsvakurudzo zvesayenzi zvikamu uye midziyo kugadzira mabhizinesi.
●Smart Test Module
Hungwaru bvunzo template editing inotsigirwa.Zvinhu zvekuyedza zvinogona kuwedzerwa zvisina tsarukano panguva yekuyedzwa uye kuchengetwa seanogona kushandiswazve purojekiti mafaera kuti uvandudze kugona kwebvunzo muchikamu chekupedzisira chekuongorora uye kubvisa.
●Kuedza otomatiki
Nekuchengetedzwa kwepa-saiti uye kuchengetedzwa kwedhijitari otomatiki bvunzo basa, zvese zviyedzo zvemudziyo mumwe chete wekudzivirira zvinogona kupedzwa nekiyi imwe.
●Multiple scanning modes
Inotsigira amplitude, chikamu, frequency, impedance, vector, kutevedzana, uye simba rinoitwa nemanyorero kana otomatiki bvunzo, zvakare inotsigira otomatiki shanduko bvunzo zvinoenderana nenzira yegradation, kutsvedza uye synthesis.
●Virtual terminal graphical kuratidza
Tsigira virtual terminal graphical kuratidza basa, kuyerera kwedata kwakajeka.
●Tumira uye gamuchira mameseji panguva imwe chete
Tsigira IEC61850-9-1, IEC61850-9-2 uye GOOSE optical digital meseji kubuda.Iyo GOOSE siginecha inogona kutumirwa nekugashirwa yakazvimiririra, uye inogona zvakare kutumira nekugashira neiyo optical Ethernet interface ine IEC 61850-9-2.
●FT3/Yakawedzerwa FT3
Tsigira FT3, FT3 kuwedzera uye DL/T 282 meseji kubuda, uye inotsigira 2M/4M/6M/8M/10M baud mwero UART encoding uye 5M/10M/20M Manchester encoding.
●Abnormal test
Iine analog meseji abnormality basa, inogona kutevedzera abnormality mumhando, kutumira frequency jitter, kunonoka anomaly, kurasikirwa kwepaketi, kunze kwenhanho, serial nhamba kusvetuka, kugadzirisa maitiro, mamiriro chaiwo shanduko uye mimwe miedzo.
●Kutadza kutamba
Inotsigira kukanganisa kutevedzera uye COMTRADE fomati yekutamba data basa.
●MMS sevhisi
Iine MMS kuverenga nekunyora basa, inogona kuverenga nekunyora yakangwara IED michina marongero uye rumwe ruzivo rwekugadzirisa.
●Nguva yekuwiriranisa uye kupa nguva
Iine synchronous trigger function, tsigiro yekuwana zvakananga kuGPS/BD antenna yenguva yekuwiriranisa, zvakare inotsigira IRIG-B, PPS uye PTP 1588 timing modhi uye inogona kutsigira yekunze kubuda IRIG-B, PPS uye PTP 1588 nguva ichipa chiratidzo.
●Zvakaoma kubata mabhinari ekuisa uye mabhinari akabuda
Huwandu hwekupinza hunoshanda uye husina kuchinjika, uye rudzi rwekupinza uye voltage yekupinda zvinozivikanwa otomatiki.Iwo machani akaparadzaniswa kubva kune mumwe nemumwe, uye iyo polarity reverse yekubatanidza ine alarm yekumhanyisa.
●Kugamuchira meseji nekuongorora
Nekugamuchira meseji uye basa rekuongorora, meseji yakagamuchirwa inogona kuvhurwa neZHNPA yekuongorora kana kutumira kunze.
●Single fiber mode
Iyo optical port inotsigira imwe-fiber kutapurirana uye imwe-fiber kugamuchira uye inotsigira optical simba rekuyedza.
●Analogi diki chiratidzo
Yakashongedzerwa neanalogi diki chiratidzo chechiratidzo, inotsigira gumi nembiri nzira analogi diki yekuisa chiratidzo, inogona kuyera -7V ~ 7V AC voltage, inotsigira gumi nemaviri nzira analogi diki inobuda chiratidzo, uye inogona kubuda -7V ~ 7V AC voltage.
●Bata kushanda
Yakashongedzerwa ne 10.4 inch yakakwirira-resolution kuratidza inotsigira kubata kubata.
●Wireless connection
Ipa kure bvunzo basa, ine WiFi module, mushandisi-ane hushamwari.
IEC 61850 yekutaurirana chiteshi | |
Function | Chero kurongeka kweIEC 61850 9-1 / 9-2 SMV kufambisa, kugamuchira kana GOOSE kutapurirana uye kugamuchira. |
Interface type | LC Optical port |
Quantity | 8 pairs, 6 pairs*100M adaptive, 2 pairs *100/1000M adaptive |
Wave urefu | 1310nm |
IEC 60044 yekutaurirana chiteshi | |
Function | GB/T 20840.8, DL/T 282, Q/GDW441 meseji kugamuchira nekutumira |
Interface type | ST |
Quantity | 6 * kutumira interface, 2 * kugamuchira interface |
Phase | |
Range | 0~360° |
Kururama | ±0.1° |
Resolution | 0.1° |
Frequency | |
Range | 0 ~ 1000Hz |
Kururama | <±0.001Hz(0~65Hz) <±0.01Hz(65~450Hz) <±0.02Hz(450~1000Hz) |
Resolution | 0.001Hz |
Nguva | |
Range | 10ms ~9999.999s |
Resolution | 1ms |
Binary contact input | |
Quantity | 8 pairi, Inogona kubatanidzwa kuneidle contact uye nekugona kubata (0 ~ 250V) |
Binary contact output | |
Quantity | 6 pairs, 2 pairs inokurumidza kubuda |
Kuputsa simba | DC250V /0.5A |
Nguva yekupindura | <100us |
Synchronize | |
Interface type | GPS/BD ANT;IRIG-B/PPS chiratidzo chemaziso;IRIG-B/PPS chiratidzo chemagetsi;IEEE 1588 |
Quantity | 1 * GPS / BD ANT; 2 * IRIG-B / PPS chiratidzo chemaziso : 1 * nguva yekuenzanisa, 1 * nguva yekupa; 2 pairs * IRIG-B / PPS chiratidzo chemagetsi : 1 pairs * nguva yekubatanidza, 1 pairs * nguva yekupa; 1 paviri* IEEE 1588 |
Wireless connection | |
Interface type | WIFI |
Wired connection | |
Interface type | 100M Lan port, RJ45 |
Quantity | 2 zvidimbu |
Analogi diki yekuisa chiratidzo | |
Interface type | Aviation plug, AC voltage |
Quantity | 12 channel |
Analogi diki chiratidzo chinobuda | |
Interface type | Aviation plug, AC voltage |
Quantity | 12 channel |
Magetsi | |
Voltage | AC/DC 220V , Kutsauka kunobvumirwa: -20% ~ 15% |
Frequency | 47~65Hz |
USB interface | |
Quantity | 2 zvidimbu |
Nzvimbo yekushanda | |
Kushanda tembiricha | -10℃~50℃ |
Humidity | ≤95%,non-condensation |
Vamwe | |
Kurema | 5.5 kg |
Dimension | 146×390×212mm(L×W×H) |
Online interface | RJ45 |
Display | 10.4 inch yechokwadi ruvara LCD touch screen |