Chengetedzo yeSeries Resonance Test System
1. Panguva yekuedzwa, chikamu chekuedza chakabatanidzwa kune-high-voltage sosi, uye tambo ye-high-voltage lead inoda kushandisa tambo yakakosha yehalo-free lead, uye chikamu chisiri chekuedza chinogadziriswa neGIS shell;
2. Muedzo unofanirwa kuve nechokwadi chokuti SF6 gasi mukamuri yegasi yegasi iri pasi pekumanikidzwa kwakarongwa, uye zvinyorwa zvegasi zviri mukati mehutano hunogamuchirwa mushure memaawa mana ekumanikidzwa kwekuwedzera kwezvinhu, uye GIS iri mumamiriro ekushanda.Muedzo unogona kuitwa chete mushure mekusimbiswa;
3. Usati wamanikidzira kuedza, iva nechokwadi chokuti mhepo inoshandura magetsi muGIS inobviswa (kana mugadziri weGIS achibvumirana, mhepo inoshandura magetsi inogona kumanikidzirwa pamwe chete, asi iyo test resonant frequency inofanira kuva yakakura kudarika 100Hz), iyo CT yechipiri pfupi yedunhu, uye kubatana kwemusungwa kunofanira kubviswa;
GDTF yakatevedzana substation frequency kutendeuka yakatevedzana resonance test system
4. Mhepo yekuedza inowedzerwa kune yakabuda bushing, iyo bushing core yakabatanidzwa kune yakakwirira voltage sosi, uye simbi bushing inobatanidzwa kune yakakosha pasi wire yegadziriro;
5. Panguva yekuedzwa, waya dzakakosha dzepasi dzinofanirwa kushandiswa pakati pezvikamu zveye test system uye pakati peye test system neGIS shell, uye pa-site yepasi bar haifaniri kushandiswa kutsiva pasi wire yekubatanidza pakati pe test system. uye GIS shell;
6. Nyatsoteerera kune imwe-point yekubatanidza pakati peye test system uye pane-saiti magetsi grid, uye nzvimbo yepasi inofanira kunge iri pamutsetse wekubatanidza pakati pevheji yemagetsi uye chinhu chekuyedza;
Iyo musimboti uye zvinhu zvinoda kutariswa kweshanduro yekunze application bvunzo
Muedzo wekunze wakaiswa bvunzo ndeyekutanga bvunzo yekuyedza iyo huru yekuvharisa yeshanduko, uye bvunzo frequency haizove yakaderera pane 80% yeiyo yakatemerwa frequency;
Kutarisa kune yekunze application bvunzo ye transformer:
1. Zvose mhepo yakaedzwa uye iyo isina-test winding ipfupi-yakatenderedzwa, uye iyo isiri-yekuedza mhepo inodzika pasi mushure mekupfupi-kutenderera.Muchidimbu, chigadzirwa chekuyedza hachifanirwe kunge chine kumiswa;
2. Panguva yekuedzwa, kuwirirana pakati pefrequency conversion resonant system uye tested transformer shell inotora iyo yakakosha pasi waya inopiwa nekambani;