Transformer Test Bhenji Kumisikidza kuKorea

Transformer Test Bhenji Kumisikidza kuKorea

Muna Zvita, 2016, HV HIPOT injiniya akazvipira kuyedza Transformer Test Bhenji muKorea.Nzvimbo yekuyedza ndeye KEPCO, inova ndiyo yakakura magetsi ekushandisa muSouth Korea, inotarisira kugadzirwa, kutapurirana uye kugovera magetsi uye kusimudzira mapurojekiti emagetsi emagetsi anosanganisira ayo ari musimba renyukireya, simba remhepo nemarasha.

Transformer Test Bench Commissioning at Korea1

Iyo transformer test bhenji inogona Kuedza inogona kuyedza icho chinhu:
22.9kV Single Phase transformers uye akakosha emagetsi,mutoro voltage uye ikozvino: AC 0-650V/78A, AC 0-1200V/29A, AC 0-2400V/14.6A.
Iyo impedance yeakaedzwa transformer iri mukati me7%, HV side iri 23kV, 11kV, 6kV.LV divi iri 0.05kV-2.4kV.

Iri bhenji rekuyedza rinogona kuitisa pazasi bvunzo
1.Hapana-mutoro bvunzo kusanganisira kwete-mutoro kurasikirwa, iyo muzana yeasina-mutoro wazvino kune yakatarwa ikozvino.
2.Muedzo wemutoro unosanganisira kurasikirwa kwemutoro, impedance voltage muzana, otomatiki tembiricha shanduko uye kurasikirwa kwemutoro bvunzo pasi pe30% kana pamusoro izere ikozvino.
3.Induced voltage test.

Transformer Test Bench Commissioning at Korea2

Features
1.Manual rekodhi bvunzo data uye chengetedza mudhatabhesi.
2.Iyo data yeNo-load bvunzo inogona kugadziriswa ne waveform uye yakayerwa voltage otomatiki.
3.Iyo data yeMutoro bvunzo inogona kugadziriswa nekupisa (75 ℃, 100 ℃, 120 ℃, 145 ℃) uye yakayerwa ikozvino.
4.MuNo-load bvunzo, LV divi voltage inogona kutariswa.
5.Muyedzo yeMutoro, HV yedivi yazvino inogona kutariswa.
6.Ese mabasa ekuyedza uye maitiro ekuyedza anogona kusarudzwa uye kudzorwa nemabhatani epamberi pepaneru.
7.Yese mhinduro dzebvunzo dzinogadziriswa zvinoenderana nezvinodiwa zveGB1094, IEC60076 kana ANSI C57.
8.Maitiro ekuyedza anogona kuenderera nePC software.
9.Yese data inogona kuchengetwa uye kudhindwa.
10.Ne zero dziviriro, over-current chengetedzo uye over-voltage kuchengetedza mabasa.
11.CT/PT renji chinja otomatiki.
12.Bhenji rekuyedza rinonyatso kudzora kune yese loop reketi uye kutarisa kuyerwa.
13.Chengetedzo alarm system.

Design
Yese inodiwa bvunzo yakashongedzerwa mubhenji rimwe chete, basa rega rega rakazvimiririra.Yese bvunzo ndeye otomatiki.
Transformer Characteristic Test (Hapana-mutoro uye Mutoro Muedzo)
Inodzorwa nePC uye inopihwa induced voltage regulator 100kVA, yepakati transformer 40kVA.

Tinogona kugadzirisa mamodheru akasiyana zvichienderana nezvinodiwa chaizvo.