GDSF-411CPD SF6 Gasi Yakazara Analyzer
GDSF-411CPD SF6gasi comprehensive analyzer chinhu chinotakurika chakagadzirirwa kuyera SF6gas dovi point, kuchena uye kuora chigadzirwa.Iyo yakakosha chikamu chine chilled girazi nzira inoshandiswa kuyedza dova point, European sensor ine infrared nzira yekuyedza SF.6gasi kuchena uye electrochemical sensor kubva kuMembrapor kuyedza SF6gasi kuora chigadzirwa.Kunze kwezvo, isu zvakare tinotora nyanzvi hardware machipisi uye yakanakisa software algorithms yeSTMicroelectronics.
SF6Humidity
Chiyero nzira | Chilled mirror nzira (Stirling Refrigeration) |
Chiyero chiyero | Dew point -100 ℃--+20℃(90s yekuyera poindi imwe chete), kukanganisa: nani pane ± 0.2 ℃ |
Kudzokorora-kugona | ± 0.1 ℃ |
Resolution | 0.01℃ |
Display unit | ℃, ppm, ℃ P20(yakashandurwa kukosha pa20 ℃) |
SF6Kuchena
Chiyero nzira | Infrared Measurement Principle (NDIR series sensors) |
Kuyera chiyero | 0 ~ 100% SF6, kukanganisa: zviri nani pane ± 0.3%FS |
Nguva yekupindura | [90%] 60s |
Kudzokorora | ± 0.3% |
Resolution | 0.01% |
Display unit | % |
SF6Decomposition Products
Chiyero nzira | Electrochemical Measurements Principle (Electrochemical series masensa kubva kuMembrapor) |
Chiyero chiyero | SO2: 0 ~ 200ppmv H2S: 0 ~ 200ppmv CO: 0 ~ 500ppmv HF: 0 ~ 50ppmv |
Kururama | SO2: 10ppmv ±3% H2S: 10ppmv ±3% CO: 50ppmv ±4% HF: 10ppmv ±3% |
Kudzokorora-kugona | SO2: 10ppmv ±2% H2S: 10ppmv ±2% CO: 50ppmv ±2% HF: 10ppmv ±2% |
Resolution | 0.01ppmv |
Display unit | ppm |
General Parameters
Magetsi | 220VAC±10%, 50Hz, AC/DC kushandiswa, kuenderera mberi kushanda kunodarika maawa masere. |
Shandisa tembiricha yezvakatipoteredza | -20--+60 ℃ |
Environment humidity | 90% RH |
Chiyereso kukosha kwesimba | Hapana mhedzisiro yekumanikidza uye kuyerera |
Dimension | 570*420*280mm |
Kurema | Kwete kupfuura 20kg. |
Main Tester | 1 chidimbu |
Adapter | 1 set |
Teflon pombi (inosanganisira kuyerera kwevhavhavha uye nekukurumidza chinongedzo) | 1 set |
Muswe pombi | 1 set |
Spare parts | 1 set |
Charger | 1 chidimbu |
Bhuku reMushandisi | 1 chidimbu |
Test Report | 1 chidimbu |